- SECTION 07223
-
- METAL BUILDING ROOF INSULATION
- NOTE ** Therm-All, Inc. ConSealTab insulation system.
- NOTE **
- NOTE ** This section is based on products manufactured by
- Therm-All, Inc., which is located at the following
- address:
- NOTE ** 31387 Industrial Parkway
- NOTE ** North Olmsted OH 44070
- NOTE ** Tel: (888) 2INSUL8
- NOTE ** Fax: (216) 734-5282
- NOTE **
- NOTE ** Therm-All, Inc. offers a complete line of
- insulation products, including the ConSealTab
- system specified in this section.
- NOTE **
- NOTE ** SECTION 07223 - METAL BUILDING ROOF INSULATION,
- Copyright 1997, The Architect's Catalog, Inc.
-
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
- NOTE ** Delete items below not required for project.
-
- A. Insulation Batts.
-
- B. Thermal Blocking.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add others as required.
-
- A. Section 07220 - Roof and Deck Insulation.
-
- B. Section 13120 - Metal Building Systems.
-
- 1.3 REFERENCES
- NOTE ** Delete references from the list below that are not
- actually required by the text of the edited
- section.
-
- A. ASTM C 236 - Standard Test Method for Steady-State
- Thermal Performance of Building Assemblies by Means of a
- Guarded Hot Box.
-
- B. ASTM C 553 - Standard Specification for Mineral Fiber
- Blanket and Thermal Insulation for Commercial and
- Industrial Applications.
-
- C. ASTM C 578 - Standard Specification for Preformed,
- Cellular Polystyrene Thermal Insulation.
-
- D. ASTM E 84 - Standard Test Method for Surface Burning
- Characteristics of Building Materials.
-
- E. ASTM E 96 - Standard Test Methods for Water Vapor
- Transmission of Materials.
-
- F. FS HH-I-558B - Insulation, Blocks, Boards, Blankets,
- Felts, Sleeving, (Pipe and Tube Covering), and Pipe
- Fitting Covering, Thermal (Mineral Fiber, Industrial
- Type).
-
- 1.4 SYSTEM DESCRIPTION
- NOTE ** Retain one or more of the following paragraphs
- specifying performance requirements for insulating
- assemblies.
-
- A. Minimum tested thermal transmittance of insulating
- assembly for nominal R-13 material, in accordance with
- ASTM C 236: R-value 9.91 (1.61 metric equivalent); U-
- value 0.101 (0.573 metric equivalent).
-
- B. Minimum tested thermal transmittance of insulating
- assembly for nominal R-13 material with thermal blocking,
- in accordance with ASTM C 236: R-value 10.57 (1.86
- metric equivalent); U-value 0.095 (0.539 metric
- equivalent).
-
- C. Minimum tested thermal transmittance of insulating
- assembly for nominal R-19 material, in accordance with
- ASTM C 236: R-value 12.08 (2.12 metric equivalent); U-
- value 0.083 (0.471 metric equivalent).
-
- D. Minimum tested thermal transmittance of insulating
- assembly for nominal R-19 material with thermal blocking,
- in accordance with ASTM C 236: R-value 16.08 (2.83
- metric equivalent); U-value 0.062 (0.352 metric
- equivalent).
-
- 1.5 SUBMITTALS
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Manufacturer's descriptive literature for
- insulation batts.
-
- C. Verification Samples: Two (2) lengths of insulation
- batt, of specified thickness, minimum length 2 feet (609
- mm).
-
- D. Quality Assurance Submittals:
- 1. Test reports: Certified reports from independent
- testing laboratory supporting compliance of
- insulating assembly to specified requirements.
- 2. Manufacturer's instructions: Printed installation
- instructions, including product storage requirements.
-
- 1.6 DELIVERY, STORAGE, AND HANDLING
-
- A. Store products of this section in manufacturer's unopened
- packaging until installation.
-
- B. Maintain storage area conditions for products of this
- section in accordance with manufacturer's instructions
- until installation.
-
- 1.7 PROJECT CONDITIONS
-
- A. Specified product requires right to left installation;
- examine project conditions, and order opposite side rolls
- for left to right installations.
-
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Acceptable Manufacturer: Therm-All, Inc.; 31387
- Industrial Parkway, North Olmsted OH 44070; ASD. Tel:
- (888) 2INSUL8, Fax: (216) 734-5282.
- NOTE ** Delete one of the two following paragraphs;
- coordinate with Division 1 requirements.
-
- B. Requests for substitution will be considered in
- accordance with provisions of Section 01600.
-
- C. Substitutions: Not permitted.
-
- 2.2 MATERIALS
-
- A. Insulation Batts:
- 1. Acceptable product: Therm-All ConSealTab.
- 2. Batt: Glass-fiber batt insulation conforming to ASTM
- C 553 and FS HH-I-558B, and bearing approval stamp of
- the following:
- a. NAIMA 202-96 (North American Insulation
- Manufacturers Association).
- b. NIA 404 (National Insulation Association).
- NOTE ** The manufacturer recommends the following facing
- type as minimum acceptable for most building
- applications; other facing are available, ranging
- from premium quality to economy. Consult with
- manufacturer for options, and review performance
- characteristics for other facings.
- 3. Facing: White polypropylene scrim kraft, standard
- duty metallized, adhered to one face of batt to form
- nominal 6 inches (152 mm) wide continuous exposed tab
- along one long edge, and nominal 6 inches (152 mm)
- wide continuous non-adhered flap along other long
- edge.
- 4. Flame spread rating, in accordance with ASTM E 84:
- 25, maximum.
- 5. Water vapor transmission, in accordance with ASTM E
- 96: 0.141 grains per hour per square foot (0.098
- grams per hour per square meter).
- NOTE ** Retain one of the following two sub-paragraphs to
- specify batt thickness.
- 6. Thickness: 4 inches (101 mm), nominal, having
- nominal R-value 13 (2.28 metric equivalent) in
- accordance with ASTM C 236.
- 7. Thickness: 6 inches (152 mm), nominal, having
- nominal R-value 19 (3.34 metric equivalent) in
- accordance with ASTM C 236.
- NOTE ** Retain one of the following two sub-paragraphs to
- specify batt width.
- 8. Batt width: Nominal 48 inches (1.2 m).
- 9. Batt width: Nominal 72 inches (1.8 m).
- 10. Roll length: 150 feet ( 45.7 m).
-
- B. Thermal Blocking: Extruded polystyrene sheet conforming
- to ASTM C 578; thickness 1 inch (25 mm) nominal.
-
-
- PART 3 EXECUTION
-
- 3.1 INSTALLATION
-
- A. Install insulation in accordance with manufacturer's
- instructions.
-
- B. Field-forming of pockets in insulation is not permitted.
-
- C. Install insulation, parallel to roof slope and
- perpendicular to purlins, progressing from eave to ridge.
- NOTE ** Delete the following paragraph if project
- conditions require left to right installation, or
- left to right installation in addition to right to
- left installation. "Opposite side" ConSealTab
- rolls will be required for left to right
- installations.
-
- D. Install insulation rows beginning from right to left.
-
- E. Roll out insulation using pipe or other device inserted
- through cardboard core of insulation roll as spindle;
- ensure that exposed tab trails direction of progress.
- NOTE ** Delete the following paragraph if thermal blocking
- not required.
-
- F. Place thermal blocks at end-to-end butt joints, covering
- joint a minimum of 4 inches (101 mm) each side of joint.
-
- G. Adjust each row of insulation to lay flat across purlins.
-
- H. As each successive row of insulation is placed, snug roll
- against previous row, pulling up exposed tab between the
- two rows.
-
- I. Beginning at end of row, pull back long edge of batt on
- previous row, allowing exposed tab to fall into place;
- smooth exposed tab down against facing from previous row,
- ensuring that tab lays flat, then drop batt from previous
- row back into place, ensuring that batts are snug against
- each other.
-
- 3.2 PROTECTION OF INSTALLED PRODUCTS
-
- A. Do not allow exposure of installed insulation to
- moisture; install only the quantity of insulation in a
- single period of construction activity that will be
- covered by roofing in that period.
-
-
- END OF SECTION
-